Modeling and Simulation of the Single Phase Voltage Source UPS Inverter With Fourth Order Output Filter
Subject Areas : Renewable energyJavad Faiz 1 , Ghazanfar Shahgholian 2 , Mehdi Ehsan 3
1 - Professor/University of Tehran
2 - Assistant Professor/Islamic Azad University - Najafabad Branch
3 - Professor/Sharif University of Technology
Keywords: Simulation, Modeling, Harmonic, UPS inverter, output Filter,
Abstract :
A UPS inverter operates in wide load impedance ranges from resistive to capacitive or inductive load. At the same time, fast transient load response, good load regulation and good switching frequency suppression is required. The variation of the load impedance changes the filter transfer characteristic and thus the output voltage value. In this paper, an analysis and simulation of the single phase voltage source uninterruptible power supply (UPS) with fourth order filter (multiple-filter) in output inverter, based on the state space averaging and small signal linearization technique, is proposed. The simulation results show the high quality sinusoidal output voltage at different loads, with THD less than %5.
_||_